General Specifications
| Use | 3 wire, 4-20mA and RS485 MODBUS output fixed point detector with in-built alarm and fault relays for the protection of personnel and plant from flammable, toxic and Oxygen hazards. Incorporates a transmitter with local display and fully configurable via non-intrusive magnetic switch interface. |
|---|---|
| Electrical | |
|---|---|
| Input Voltage Range | 12 to 32VDC (24VDC nominal) |
| Max Power Consumption | Maximum power consumption is dependent on the type of gas sensor being used. Electrochemical cells = 3.7W, IR = 3.7W and catalytic = 4.9W. Maximum inrush current = 800mA at 24VDC |
| Current Output Relays | Sink or source 3 x 5A@250VAC. Selectable normally open or normally closed (switch) and energized/de-energised (programmable) Alarm relays default normally open/de-energized. Fault relay default normally open/energized |
| Communication | RS485, MODBUS RTU |
| Construction | |
|---|---|
| Material | Housing: Epoxy painted aluminium alloy ADC12 or 316 stainless steel Sensor: 316 stainless steel |
| Weight (approx) | Aluminium Alloy LM25: 4.4lbs 316 Stainless Steel: 11lbs |
| Mounting | Integral mounting plate with 4 x mounting holes suitable for M8 bolts. Optional pipe mounting kit for horizontal or vertical pipe Ø1.5 to 3" (2" nominal) |
| Cable Entries | UL\cUL versions: 2 x ¾”NPT conduit entries. Suitable blanking plug supplied for use if only 1 entry used. Seal to maintain IP rating; ATEX/IECEx versions: 2 x M20 cable entries |
| Environmental | |
|---|---|
| IP Rating | IP66 in accordance with EN60529:1992 |
| Certified Temperature Range | -40ºF to +149ºF (-40ºC to +65ºC) |
| Detectable Gases and XCD Sensor Performance | |||||
|---|---|---|---|---|---|
| Gas | Default Range | Steps | Default Cal Point | Response Time (T90) Secs | Accuracy |
| Electrochemical Sensors | |||||
| Oxygen | 25.0%Vol. | n/a | 20.9%Vol. | <30 | <±0.5%Vol. |
| Hydrogen Sulfide* | 50.0ppm | 0.1ppm | 25ppm | <50 | <±1ppm |
| Carbon Monoxide** | 300ppm | 100ppm | 100ppm | <30 | <±6ppm |
| Hydrogen | 1,000ppm | n/a | 500ppm | <65 | <±25ppm |
| Nitrogen Dioxide*** | 10.0ppm | 5.0ppm | 5.0ppm | <40 | <±3ppm |
| * Lowest Alarm Limit = | 1ppm; Lowest Detection Limit = .5ppm | ||||
| ** Lowest Alarm Limit = | 15 ppm; Lowest Detection Limit = 10ppm | ||||
| *** Lowest Alarm Limit = | 0.6 ppm; Lowest Detection Limit = 0.3ppm | ||||
| Catalytic Bead Sensors | |||||
|---|---|---|---|---|---|
| Flammable 1 to 8 | 100%LEL | 10%LEL | 50%LEL | <25 | <±1.5%LEL |
| Infrared Sensors | |||||
|---|---|---|---|---|---|
| Methane | 100%LEL | 10%LEL | 50%LEL | <30 | <±1.5%LEL |
| Propane | 100%LEL | 10%LEL | 50%LEL | <30 | <±1%LEL |
| Carbon Dioxide | 2%Vol. | n/a | 1%Vol. | <30 | <±0.04%Vol |
| Certification | |
|---|---|
| US, Latin America, Canada | UL/c-UL - Class I, Division 1, Groups B, C and D, Class I, Division 2, Groups B, C & D, Class II, Division 1, Groups E, F & G, Class II, Division 2, Groups F & G. -40°C to +65°C |
| European | ATEX Ex II 2 GD Ex d IIC Gb T6 (Ta -40ºC to +65ºC) Ex tb IIIC T85°C Db IP66 |
| International | IEC Ex d IIC Gb T6 (Ta -40ºC to +65ºC) Ex tb IIIC T85°C Db IP66 |
| EMC | CE: EN50270:2006 EN6100-6-4:2007 |
| Performance | UL508; CSA 22.2 No. 152 (flammable gasses, excludes infrared sensors); ATEX, IEC/EN60079-29-1:2007, EN45544, EN50104, EN50271; China: PA Pattern Measurement (for transmitter and toxic gas sensors) “CCCF” Shenyang for Flammable (fire dept approval) |