Beacon 200

Controllers in the Beacon Series come in single- or multi-channel options, with sensors being mounted either directly to the controller or wired remotely. All of the Beacon Series controllers are compatible with RKI LEL, O2, and CO sensors, with some Beacon controllers capable of integrating sensors for other toxic and non-toxic gasses.
Each Beacon controller has an audible built-in alarm and is in a weatherproof enclosure.

General Specifications

Physical
DimensionsHeight: 10.5” (267 mm) x Width: 8.5” (216 mm) x Depth: 6.3” (158 mm)
EnclosureWall mounting grey polycarbonate with hinged cover
Conduit Connection3/4” NPT conduit hubs, 3 provided. 2 for sensor wiring and 1 for power & relay wiring
Wiring TerminationScrew type terminal block, 14 gauge max
Power115 VAC or 24 VDC standard, Optional 230 VAC. Battery backup option available
Controls4 internal push buttons for setup, programming, and calibration. 1 external push button for alarm reset
Operating Environment
Operating Temperature-4°F to 122°F (-20°C to 50°C)
Storage Temperature-4°F to 158°F (-20°C to 70°C)
Enclosure RatingNEMA-4X enclosure, waterproof, chemical, and weather resistant. Suitable for indoor and outdoor installations.
Inputs
Direct Wired SensorsLEL, Oxygen, and toxic gas sensors. Remote amp required for greater than 500 feet
4-20 mA SensorsAccepts any 4-20 mA transmitter (24 VDC, 2 or 3 wire). A wide variety of RKI/Riken sensors are available with 4-20 mA signals; (See list of detectable gases.) Wiring distances up to 5,000 feet
Sampling MethodsAccepts diffusion or sample draw heads
Outputs
Relays7 relays - 10 amp rating (at 115 VAC), SPDT isolated contacts. 2 relays for gas alarm levels per channel, plus 2 relays for common gas alarm and 1 common relay for malfunction. Relays fully programmable for: increasing or decreasing alarm, latching or self reset, normally energized or normally de-energized, time delay for alarm on and alarm off
4-20 mASignal output, 4-20 mA (into 1,000 ohms impedance maximum), per channel
24 VDC24 VDC (350 mA max) output provided to operate sample drawing adapters
DisplayAlphanumeric display with backlighting. 20 characters per line; 4 lines each
AudibleBuilt-in audible alarm, 94 dB, mounted on enclosure Coded output: pulsing = gas alarm, steady = fail
Visual4 LED’s on the front cover for alarm status indication, pilot, and malfunction
Approvals and Warranty
ApprovalsCSA Certified to CSA C22.2 No. 1010 and ANSI/ISA S82.01
WarrantyOne year material and workmanship