General Specifications
Outputs | |
---|---|
Relays | 12 amp rated contacts for each alarm |
Audible | 85 db alarm at 10 cm |
Visual | Alarm 1: Orange LED Alarm 2: Red LED |
Environmental | |
---|---|
Operating Temp | 35°F to 120°F (2°C to 49°C) |
Relative Humidity | 10 - 95% RH, non condensing |
Physical | |
---|---|
Dimensions | Height: 6.85” 174 mm Width 6.48” 165 mm Depth 3.30” 84 mm |
Enclosure | ABS plastic, indoor housing |
Sensors | |
---|---|
Sensor Types | Metal Oxide Semiconductor type (MOS) |
Measuring Ranges | LEL levels available for many gases. Typically set to 10% LEL for alarm 1, and 25% or 30% LEL for alarm 2 (Highest possible setting is 30% LEL). |
Sensor Connector | Sensor is connected to 30ʼ extension cable wired to terminals inside unit. Cable length can be decreased or increased as needed. |
Power and Warranty | |
---|---|
Power | 24 VDC (standard) 115 VAC or 48 VDC (optional) |
Warranty | One year materials and workmanship |
Partial List Of Detectable Gases | |
---|---|
Many other gases available. | Contact RKI for gases not listed |
Ethyl Alcohol | C2H5OH |
Hexane | C6H14 |
Hydrogen | H2 |
Iso-Butane | i-C4H10 |
Isopropyl Alcohol | (CH3)2CHOH |
Methane | CH4 |
Propane | C3H8 |