General Specifications
Product Specifications | |
---|---|
Product Type | 64 Channel wired Modbus gas monitoring controller |
Operating Voltage | 12V to 35V DC (standard) |
Power Type | Wired power |
Power Supply | 6.25A (150W), 85/264V AC to 24V DC (optional) |
Current Draw | 275 mA maximum (at 24V DC) |
Display Screen | 160 x 104 Resolution graphical LCD screen transflective (sunlight readable) with LED back light |
Interface | 3 Push-buttons (MENU, ADD, SUB, SCAN/HOLD and RESET/ESC) |
Product Mounting | 4 Mounting feet, 6 in. W x 12-1/4 in. T (included) maximum mounting bolt/screw size of 5/16 in. (8mm) diameter |
Temperature Range | -20°C to +70°C (-4°F to +158°F) |
Product Capability | M2A, T3A, VOC Pro transmitters |
Digital Input | Up to 64 individual RKI gas detectors using RS-485 Modbus |
Relays | • 4 Dry-contact relays with 4 amp replaceable fuses • Fault terminal • Optional to disable alarm relay • Latching and non-latching relay settings |
Enclosure Materials | NEMA-4X enclosure, waterproof, chemical, and weather resistant |
Wiring Hubs | Supplied with two 3/4” conduit hubs on bottom of housing. Can be located on sides or top if specified when ordering. |
Accessories | Optional horn and/or strobe on housing (uses 1 or 2 of available relays) |
Product Dimensions | 10 in, L x 8 in. W x 6 in. H (Max. dimensions with attachments) |
Total Weight | 8.5 lbs |
Hardware Warranty | 1-Year Limited |